V8 Series
Burnham's V8 oil-fired boiler is designed for quiet operation while providing years of reliable and efficient service. The jacket design and burner enclosure give the V8 a modern, finished appearance. It is available in multiple heating capacities that can be configured for water or steam - with or without a tankless hot water heating coil. As one of the most versatile boilers available, the V8 is intended for installation in a wide variety of home styles and sizes. 70 To 298 MBH capacity.
| Boiler Number |
DOE Heating Cap. MBH |
AFUE % |
I=B=H* Net Ratings MBH |
Burner Cap. GPH |
Vent Dia. (in) |
| V-82 |
70 |
82.1 |
61 |
0.60 |
6 |
| V-83 |
91 |
86.0 |
79 |
0.75 |
6 |
| V-84 |
127 |
86.1 |
110 |
1.05 |
7 |
| V-85 |
164 |
86.2 |
143 |
1.35 |
7 |
| V-86 |
201 |
86.3 |
151 |
1.65 |
8 |
| V-87 |
252 |
85.0 |
219 |
2.10 |
8 |
| V-88 |
275 |
- |
239 |
2.35 |
8 |
| V-89 |
299 |
- |
260 |
2.60 |
9 |
* Gross Output
| Boiler Model |
Burner Cap. GPH |
DOE Heat. Cap. MBH |
I=B=R Net Ratings MBH |
Min. Chimney Requirements |
AFUE % |
| Water MBH |
Steam MBH |
Steam Sq Ft |
Dia. (round) |
Rect. (in inches) |
Height (ft) |
Water |
Steam |
| V-82 |
0.60 |
70 |
61 |
- |
- |
6 |
8 x 8 |
15 |
82.1 |
- |
| V-83 Water |
0.75 |
91 |
79 |
68 |
283 |
6 |
8 x 8 |
15 |
86.0 |
85.1 |
| V-83 Steam |
1.05 |
123 |
107 |
- |
- |
6 |
8 x 8 |
15 |
82.6 |
- |
| V-84 Water |
1.05 |
127 |
110 |
95 |
396 |
7 |
8 x 8 |
15 |
86.1 |
85.3 |
| V-84 Steam |
1.35 |
159 |
138 |
- |
- |
7 |
8 x 8 |
15 |
83.2 |
- |
| V-85 Water |
1.35 |
164 |
143 |
123 |
512 |
7 |
8 x 8 |
15 |
86.2 |
85.4 |
| V-85 Steam |
1.65 |
196 |
170 |
- |
- |
7 |
8 x 8 |
15 |
83.9 |
- |
| V-86 Water |
1.65 |
201 |
175 |
151 |
629 |
8 |
8 x 8 |
15 |
86.3 |
85.7 |
| V-86 Steam |
1.90 |
227 |
197 |
- |
- |
8 |
8 x 8 |
15 |
84.6 |
- |
| V-87 |
2.10 |
252 |
219 |
189 |
787 |
8 |
8 x 8 |
15 |
85.0 |
84.7 |
| V-88 Water |
2.35 |
275 |
239 |
- |
- |
8 |
8 x 12 |
15 |
- |
- |
| V-88 Steam |
2.35 |
266 |
- |
200 |
833 |
8 |
8 x 12 |
15 |
- |
- |
| V-89 Water |
2.60 |
299 |
260 |
- |
- |
9 |
8 x 12 |
15 |
- |
- |
| V-89 Steam |
2.60 |
298 |
- |
224 |
933 |
9 |
8 x 12 |
15 |
- |
- |
V8 Information and Documentation

Product Line Card | Radiant Heating Services | Who To Talk To | Showroom
Terms and Conditions | Employment Positions | Join Our Email List | Help